LEAD IN MEDICAL SERVICE
It is found in a large number of pieces of medical equipment, in particular in imaging and treatments using ionising radiation.
We provide a complete range of products:
- lead sheets of all thicknesses
- boards cut to your dimensions
- lead blocks
- machined parts
- screening
PARTITION FOR RADIOLOGY ROOM
BA13 + lead board
Format: 2200 x 600 – Adhesion of the lead under factory pressure
Thicknesses available are: 0.5, 1, 1.5, 2 and 3 mm.
The thickness of lead sheets (protection strip and boards) is determined by the customers.
WEIGHT OF BOARDS
Thickness 0.5 mm 1 mm 1.5 mm 2 mm 3 mm
Weight 22 kg 29 kg 38 kg 46 kg 62 kg
IMPLEMENTATION PRECAUTIONS :
Framework :
The struts are provided with a 0.60 ml spacing.
The wall on the radiology room side is made up of a board of BA13 + lead of thickness 0.60 ml and 1 board of BA13 of thickness 1.20 ml.
The continuity of protection to the right of the vertical joints will be provided by a protection strip of thickness 0.5 mm for BA13 + lead boards of 0.5 mm or, by a protection clip for greater thicknesses of lead.
Near electrical equipment, they will be provided with protection sumps.